Description for Honeywell L8148A1017
Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.
Features
High limit opens burner circuit only. Include transformer and accessory terminals for adding a remote low limit controller. Case available for horizontal or vertical mounting. Requires a 24 Vac thermostat with heat anticipator set at 0.2A. TRADELINE models include well adapter, tube of heat conductive compound and range stops. Product Specifications Description: High Limit Aquastat Relay with 8 F fixed differential
Application: High Limit
Operating Range, High Limit (F): 120 F to 240 F
Operating Range, High Limit (C): 54 C to 116 C
Differential Temperature (F): 8 F fixed
Setpoint Temperature Range (F): 240 F
Setpoint Temperature Range (C): 116 C
Switching Action: SPST: High Limit & Circulator
Anticipator Setting: 0.2 A
Maximum Operating Pressure (psi): Immersion Well: 255 psi
Maximum Operating Pressure (kPa): Immersion Well: 1757 kPa
Electrical Ratings (burner AFL): Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 Vac
Electrical Ratings (burner ALR): Line Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac
Electrical Ratings (burner millivolt): 0.25 A @ 1/4 to 12 Vdc
Electrical Ratings (circulator AFL): 7.4 A @ 120 Vac
Electrical Ratings (circulator AFL): 3.7 A @ 240 Vac
Electrical Ratings (circulator ALR): 44.4 A @ 120 Vac
Electrical Ratings (circulator ALR): 22.2 A @ 240 Vac
Voltage: 120 Vac
Frequency: 60 Hz
Capillary Length (in.): 4 1/2 in.
Capillary Length (mm): 114 mm
Dimensions (in.): 4 5/16 in. high x 6 1/8 in. wide x 3 1/8 in. deep
Dimensions (mm): 110 mm high x 156 mm wide x 79 mm deep
Insulation Depth (in.): 1 1/2 in. to 3 in. less well.
Insulation Depth (mm): 38 mm to 76 mm less well
Mounting: Horizontal
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Maximum Ambient Temperature (F): 150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
Maximum Ambient Temperature (C): 66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load
Electrical Connections : Quick-Connect / Screw
Approvals, Underwriters Laboratories Inc : UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.
Approvals, Canadian Standards Association: Certified: File No. LR1620, Guide No. 400-E-O
Tradeline Value : Tradeline