Specs

Application: High Limit
Switch Action: SPST
Electrical Rating: Burner: 7.4 A @ 120 Vac
Burner: 3.7 A @ 240 Vac
0.25 A @ 0.25 to 12 Vdc
Circulator: 7.4 A @ 120 Vac
Circulator: 3.7 A @ 240 Vac
Electrical Ratings (ALR): Burner: 44.4 A @ 120 Vac
Circulator: 44.4 A @ 120 Vac
Burner: 22.2 A @ 240 Vac
Circulator: 22.2 A @ 240 Vac
Temperature Range (F): 120°F to 240°F
Differential:
?
8°F
Fixed
Height: 6-1/8"
Width: 4-3/8"
Depth: 3-1/8"
Operating Humidity: 0% to 95% (non-condensing)
Mount: Vertical
Horizontal
Max Ambient: 77F with 1.4A 24V Load
150F with 1.2A 24V Load
Connection Type: Quick-Connect
Capillary Length: 4-1/2"
Anticipator Rating: 0.2 A
Voltage:
?
120v
Frequency: 60 Hz
Max PSI:
?
255 psi @ Immersion Well

Description for Honeywell L8148J1009

Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.
Features

  • High limit opens burner circuit only.
  • Include transformer and accessory terminals for adding a remote low limit controller.
  • Case available for horizontal or vertical mounting.
  • Requires a 24 Vac thermostat with heat anticipator set at 0.2A.
  • TRADELINE models include well adapter, tube of heat conductive compound and range stops.

  • Product Specifications
    Description : Aquastat Relay with 8 F fixed differential
    Application : Aquastat Relay
    Operating Range, High Limit (F) : 120 F to 240 F
    Operating Range, High Limit (C) : 54 C to 116 C
    Differential Temperature (F) : 8 F fixed
    Setpoint Temperature Range (F) : 240 F
    Setpoint Temperature Range (C) : 116 C
    Switching Action : SPST: High Limit & Circulator
    Anticipator Setting : 0.2 A
    Maximum Operating Pressure (psi) : Immersion Well: 255 psi
    Maximum Operating Pressure (kPa) : Immersion Well: 1757 kPa
    Electrical Ratings (burner AFL) : 7.4 A @ 120 Vac
    Electrical Ratings (burner AFL) : 3.7 A @ 240 Vac
    Electrical Ratings (burner ALR) : 44.4 A @ 120 Vac
    Electrical Ratings (burner ALR) : 22.2 A @ 240 Vac
    Electrical Ratings (burner millivolt) : 0.25 A @ 1/4 to 12 Vdc
    Electrical Ratings (circulator AFL) : 7.4 A @ 120 Vac
    Electrical Ratings (circulator AFL) : 3.7 A @ 240 Vac
    Electrical Ratings (circulator ALR) : 44.4 A @ 120 Vac
    Electrical Ratings (circulator ALR) : 22.2 A @ 240 Vac
    Voltage : 120 Vac
    Frequency : 60 Hz
    Capillary Length (in.) : 4 1/2 in.
    Capillary Length (mm) : 114 mm
    Dimensions (in.) : Vertical Mount: 6 1/8 in. high x 4 5/16 in. wide x 3 1/8 in. deep
    Dimensions (in.) : Horizontal Mount: 4 5/16 in. high x 6 1/8 in. wide x 3 1/8 in. deep
    Dimensions (mm) : Vertical Mount 156 mm high x 110 mm wide x 79 mm deep
    Dimensions (mm) : Horizontal Mount: 110 mm high x 156 mm wide x 79 mm deep
    Insulation Depth (in.) : 1 1/2 in. to 3 in. less well.
    Insulation Depth (mm) : 38 mm to 76 mm less well
    Mounting : Horizontal or Vertical
    Operating Humidity Range (% RH) : 0 to 95% RH, non-condensing
    Maximum Ambient Temperature (F) : 150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
    Maximum Ambient Temperature (C) : 66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load
    Electrical Connections : Quick-Connect / Screw
    Approvals, Underwriters Laboratories Inc : UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.
    Approvals, Canadian Standards

    Aquastat Relay, 8°F differential

    REVIEW SNAPSHOT®

    by PowerReviews
    Honeywell Aquastat Relay, 8°F differential
     
    5.0

    (based on 6 reviews)

    Ratings Distribution

    • 5 Stars

       

      (6)

    • 4 Stars

       

      (0)

    • 3 Stars

       

      (0)

    • 2 Stars

       

      (0)

    • 1 Stars

       

      (0)

    100%

    of respondents would recommend this to a friend.

    Pros

      Cons

        Best Uses

            • Primary use:
            • Personal (6)

          Reviewed by 6 customers

          Sort by

          Displaying reviews 1-6

          Back to top

           
          5.0

          right on the money

          By Wild Bill

          from Dover, NH

          Verified Buyer

          Pros

            Cons

              Best Uses

                Comments about Honeywell Aquastat Relay, 8°F differential:

                I have a 25 year old boiler and after troubleshooting, found the Aquastat relay and gas valve were shot. I searched locally and found supply houses were not helpful as the model was old and had been replaced and I could not get a straight answer. I contacted Pex Supply after doing an online search and they cheerfully gave me the correct model replacement and the best price I could find online!! The only complaint was that the online chat to get the info on a replacement took nearly 3 days to hear back from. In the meantime I was without heat, so on day 2 with no response, I chose to call their toll free # and got an immediate answer. Thanks Pex!!!!

                • Primary use:
                • Personal
                 
                5.0

                Easy instructions on how to install

                By none

                from Aurora IL

                Verified Buyer

                Pros

                  Cons

                    Best Uses

                      Comments about Honeywell Aquastat Relay, 8°F differential:

                      Item works well and good price .

                      • Primary use:
                      • Personal
                       
                      5.0

                      exact replacement

                      By Rich the handyman

                      from New Jersey

                      Verified Buyer

                      Pros

                        Cons

                          Best Uses

                            Comments about Honeywell Aquastat Relay, 8°F differential:

                            I had to replace this aquastat after 36 years due to burned contacts on the relay for the circulator pump. It is an exact replacement which is now working perfectly. How often do you get 36 years out of a part and find an exact match?

                            • Primary use:
                            • Personal
                             
                            5.0

                            Keeps my family warm again

                            By Jim in PA

                            from McKean PA

                            Verified Buyer

                            Pros

                              Cons

                                Best Uses

                                  Comments about Honeywell Aquastat Relay, 8°F differential:

                                  My 25 year old hydrotherm boiler keeps working fine with a few new parts. Hope it lasts as long as the original Honeywell aquastat did, so my grandkids will have to change it next time.

                                  • Primary use:
                                  • Personal
                                   
                                  5.0

                                  I would buy this product again

                                  By sprdty

                                  from Michigan

                                  Verified Buyer

                                  Pros

                                    Cons

                                      Best Uses

                                        Comments about Honeywell Aquastat Relay, 8°F differential:

                                        Easy to install and works great. Excellent replacement cost value.

                                        • Primary use:
                                        • Personal
                                         
                                        5.0

                                        Perfect Replacement

                                        By RT Metalbender

                                        from Somerville, NJ

                                        Verified Buyer

                                        Pros

                                          Cons

                                            Best Uses

                                              Comments about Honeywell Aquastat Relay, 8°F differential:

                                              New one was perfect. Old one was a PITA to remove. The probe was stuck in the fitting. Took it out and to the garage. Put a torch on it and no problem.

                                              • Primary use:
                                              • Personal

                                              Displaying reviews 1-6

                                              Back to top

                                              Q&A: Ask the Questions, share answers

                                              Do you have questions about this product?

                                              get answers from real customers and in-house experts with AnswerBox.

                                              9 Questions | 9 Answers
                                              Displaying questions 1-9
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                I have a old one L8148E-1216. Can I use the New one like L8148J 1009?
                                                Asked on 3/1/2012 by ptf from Brooklyn ny

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  L8148E1265 (which has a Molex plug for use with vent dampers) is the recommended replacement for the obsolete L8148E1216.

                                                  Answered on 3/2/2012 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                which aquastat do you recomend to peplace honey well 842A-16
                                                Asked on 12/16/2011 by rady from queens ny

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  842A-16 is a White-Rodgers part that has no listed replacement.

                                                  Answered on 12/19/2011 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                Does this relay replace the Honeywell L8148B which is out of production?
                                                Asked on 7/19/2011 by Anonymous

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  Yes, the manufacturer lists this as the replacement for L8148B models.

                                                  Answered on 7/19/2011 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                where does the 12v dc rating come from in your product review column? or is the the rating for no power to mill gas vavle rating. thanks
                                                Asked on 4/15/2011 by ace from manchhester, ct.

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  According to the manufacturer, these are the Electrical Ratings (burner millivolt).

                                                  Answered on 4/15/2011 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                Is it recommended to change the immersion well at the same time as replacement of the aquastat, L8148J1009, and if so what is the correct replacement # to use
                                                +
                                                Asked on 2/8/2011 by george from cumberland, md.

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  Yes, it is recommended. For a ½” well, use part 121371A , and use part 121371B with ¾” wells.

                                                  Answered on 2/8/2011 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                will this replace L8048E need to replace
                                                Asked on 1/9/2011 by Dave from Bunker Hill Il 62014

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  As per Honeywell, the following relays can be replaced by the L8148J1009: L8048E1027, L8048E1035, L8048E1043, L8048E1076, L8048E1092, L8048E1K0A, and L8048E2K0A.

                                                  Answered on 1/20/2011 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                I just had my Honeywell Aquastat Relay L8148E replaced with the L8148J. Apparently this is the direct replacement since the L8148E is discontinued (according to the Honeywell web site). The boiler comes with the automatic vent damper. My HVAC guy replaced the Aquastat and connected the wires just like the old one. However the boiler did not work properly. Even when the thermostat did not call for heat the boiler would still turn on. After some trouble shooting, my HVAC guy told me that it appears that the new Relay L8148J must have some internal ground, and the ground (green wire) that goes from the burner (screwed on the burner) to the GDN (Burner) on the Module (black box on the boiler) was causing this problem. When he disconnected the green wire (GDN burner) everything seems to work just fine. Is this true? Do the L8148J have some internal grounding that would cause this problem.

                                                The person in Colorado (see above) appears to have the same problem.
                                                Asked on 11/30/2010 by sb from chicago

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  The L8148E is still available with a vent damper plug. If you are experiencing issues with the L8148J that was installed, we recommend replacing it with either the L8148E1257 or the L8148E1265, both which are still available.

                                                  Answered on 12/7/2010 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                Can Aquastat relay L8148J replace Aquastat relay L8148E?
                                                Our plumber told the electrician it was OK to take out the L8148E and replace it with the L8148J. They are working on it now and have high over heating and high pressure and trouble shooting. Adjusting the temp indicator does not have any effect, temp just keeps going up super high. A licensed/union plumber and licensed/union electrician. They thought it would be no problem, since they had the aquastat L8148J on hand. I think they need to get the exact model# aquastat that they took out.
                                                Asked on 11/5/2010 by Liz from Colorado Springs, CO

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  The difference between the units is that the "E" model has an operating range of 180 to 240 degrees and a temperature differential of 15 degrees, while the "J" model has an operating range of 120 to 240 degrees and a temperature differential of 8 degrees. It sounds like some temperature setting may need to be changed.

                                                  Answered on 11/9/2010 by PexSupply Staff from NY
                                              • Honeywell Aquastat Relay, 8°F differential

                                                Q:

                                                Is your Honeywell L8148J1009 a replacement for L8148J
                                                Asked on 8/26/2010 by Anonymous from Farmersburg In.

                                                1 answer

                                                • CUSTOMER CARE

                                                  A:

                                                  Yes, SKU # L8148J1009 is the replacement unit for SKU #L8148J.

                                                  Answered on 8/26/2010 by PexSupply Staff from NY
                                              Displaying questions 1-9

                                              Do you have a question about this product? 

                                              PexSupply.com Logo

                                              Join Our Mailing List - Sign up and receive special offers and coupons

                                              Nextag Seller PriceGrabber User Ratings for Pex Supply PHCC BBB Reliability Seal
                                              HACKER SAFE certified sites prevent over 99.9% of hacker crime. Facebook Twitter Youtube